Professional High Voltage Test Equipment Manufacturer

Home
Products
About Us
Factory Tour
Quality Control
Contact Us
Request A Quote
Home ProductsPartial Discharge Test Equipment

Live XLPE Cable Partial Discharge Test Equipment , Patrol Type Pd Testing Equipment

Live XLPE Cable Partial Discharge Test Equipment , Patrol Type Pd Testing Equipment

Live XLPE Cable Partial Discharge Test Equipment , Patrol Type Pd Testing Equipment
Live XLPE Cable Partial Discharge Test Equipment , Patrol Type Pd Testing Equipment Live XLPE Cable Partial Discharge Test Equipment , Patrol Type Pd Testing Equipment Live XLPE Cable Partial Discharge Test Equipment , Patrol Type Pd Testing Equipment Live XLPE Cable Partial Discharge Test Equipment , Patrol Type Pd Testing Equipment Live XLPE Cable Partial Discharge Test Equipment , Patrol Type Pd Testing Equipment

Large Image :  Live XLPE Cable Partial Discharge Test Equipment , Patrol Type Pd Testing Equipment Get Best Price

Product Details:
Place of Origin: China
Brand Name: Fanke High-Voltage
Certification: ISO9001
Model Number: PPD8609A
Payment & Shipping Terms:
Minimum Order Quantity: One unit
Price: 15000~25000 USD /Unit
Packaging Details: Export standard wooden case with fumigation free
Delivery Time: 20~25 work days
Payment Terms: L/C, T/T
Supply Ability: 10units/month
Detailed Product Description
Test Principle: High-frequency Current Sensor (HFCT) Measurement And Ultrasonic Detecting Technology Usage: Patrol Type Partial Discharge Detecting Tester For Live XLPE Cable And Power Transformer
Refer Standard: GB / T 7354 Partial Discharge Measurement ;DL/T 417 Guideline For Local Measurement Of Partial Discharge Of Electric Equipment ;
High Light:

pd testing equipment

,

partial discharge test set

Patrol type Partial Discharge Detecting Tester For Live XLPE cable And Power Transformer

 

 

1. Product introduction:

Due to manufacturing or installation defects, discharge occurs in the insulated portion of the live cable end (joint) until insulation breakdown damage occurs, and even a fire or explosion at uncertain defects may occur. Therefore, how to find the hidden troubles before the accident is the key to solve the problem, which makes the discharge detection necessary for live cable.

 

The model PPD8209A is a kind of high-frequency partial discharge inspection instrument which adopts the high-frequency current and ultrasonic detection methods for PD inspection and detecting to live MV/HV cable and transformer through HFCT (high-frequency current transformer) or Ultrasonic transducer. It has the feature of small volume, excellent performance and easy operation.

 

The PD tester adopts modern electronic and computer integrated technology to realize signal amplification (analog, electronic, digital), filtering, data acquisition, data processing, graphic display, test report automatic generation, thus completing the measurement and analysis of partial discharge.

 

2. Reference Standard

GB 7354 Partial discharge measurement

DLT 417 Guideline for local measurement of partial discharge of electric equipment

GBT 16927.1 High voltage test technology Part 1: General test requirements

GBT 16927.2 High voltage test techniques Part 2: Measuring system

GB T 16927.3 High voltage test techniques Part 3: Definition and requirements of field test

 

3.Main Components:

SN Name Specifications Qty
1 Patrol type Partial Discharge Detecting Tester PPD8209A 1pcs
2 Charger for host machine   1pcs
3 High-frequency current sensor HFCT 1pcs
4 Ultrasonic sensor Just for live power transformer 1pcs
5 Cable ultrasonic detector With 1pcs
6 Coaxial cables 50Ω 2pcs
7 Wireless sync transmitters and power cords.   1set
8 Data storage card reader.   1pcs
9 signal coupling agent For Ultrasonic sensor 1pcs
10 Storage transport case.   1pcs
 

 

4. Detecting principle and method:

4.1 High-frequency current sensor measurement principle

The high-frequency current sensor is mainly used for partial discharge detection of high-voltage electrical equipment, and adopts the principle of pulse current. Since most high-voltage electrical equipment has distributed capacitance on its high and low voltage side or grounded part, when a high electric field strength area discharge takes place, the discharge signal is coupled to the grounding part and enters the earth through the grounding line. The HFCT sensor is clamped on the ground line and detects the pulse current signal generated by the PD, thereby obtaining partial discharge information of the device during test. It is mainly used for partial discharge signal detection of medium and high voltage equipment such as cables, transformers, reactors, GIS, switch-gear.

 

4.1.1 High frequency current detection for XLPE Cable

Due to manufacturing or installation defects, discharge occurs in the insulated portion of the cable end joint until insulation breakdown damage occurs, and even a fire or explosion may occur. Therefore, how to find the hidden troubles before the accident is the key to solve the problem, which makes the charge detection necessary.

In high-voltage cables, the wires and the metal sheath shield are separated by an insulating material to form a distributed capacitance, which is about several hundred pF, forming a path for high-frequency signals. Therefore, the high-frequency partial discharge signal is transmitted by the distributed capacitance to the ground lead. When the internal discharge occurs, a high-frequency pulse current is generated, and the high-frequency pulse current flows through the distributed capacitance between the core and the metal sheath , from the high-potential core to the low-level metal shield. On the sleeve , and enter the ground through the cable intermediate connector or the ground wire at the terminal. Therefore, a high-frequency current transformer sensor is connected to the grounding wire at the intermediate joint or terminal to couple the high-frequency pulse partial discharge current into the sensor and pass through the test cable between the sensor and the patrol instrument. The PPD8209A inspection tester performs signal acquisition and analysis.

The indication figure for live cable or live cable joint is as following :

 

4.2. Ultrasonic (US) measurement principle

When a partial discharge signal is generated inside the power equipment, vibration and sound of the impact are generated. Ultrasonic methods measure partial discharge signals by mounting an ultrasonic sensor on the outer wall of the device chamber. The method is characterized in that the sensor has no connection with the electrical circuit of the geographical equipment, and is not interfered by the electrical appliance, but is susceptible to the surrounding environment noise or the mechanical vibration of outside equipment when used in the field. Since the ultrasonic signal has a large attenuation in the commonly used insulating materials of the power equipment, the detection range of the ultrasonic detecting method is limited, but has the advantage of high PD positioning accuracy.

 

4.2.2 Ultrasonic detecting PD for live cable

For live high voltage cables, in many cases, due to the poor quality of the cable itself or cable accessories, external force damage and mechanical damage, corrosion and moisture, cable joint construction quality problems, accessories aging and other reasons, the cable joint is prone to partial discharge. Therefore, it is necessary to perform partial discharge detection on high voltage cables.

 

The PPD8609A tester is a device for detecting a discharge fault of a high voltage cable or cable joint .The detector of the tester adopts an acoustic-electric three-dimensional spatial positioning sensor, and can realize the three-dimensional spatial position and the discharge strength of the discharge point under a condition of not contacting the cable under test. Therefore, the insulation condition of the measured cable point will be judged, and the occurrence of the accident is prevented in advance. This detecting method usually can be applied to on-line detection and positioning of partial discharge of cable ends and cable distribution boxes.

 

5.General Technical data:

Host machine feature  
Number of detecting channels 2channels,1 for HFCT method detecting,1 for US method detecting
Sampling accuracy 12bit
Trigger mode Internal synchronization and external synchronization
HFCT measuring technical feature  
Detection bandwidth 100K-50MHz
Transmission impedance >5mV/mA(10MHz )
Output impedance 50Ω
Detection sensitivity 5pC
Detection range for discharge -20-80dB
Measurement error ±1dB
resolution 1dB
Signal input interface Standard BNC through coaxial cable
Measuring display mode for PD signal Waveform mode, statistical mode,impulse mode
Ultrasound measuring technical feature
Detection frequency range 20kHz-300kHz
Output impedance 50Ω
Detection sensitivity 0.1mV
Detection range for discharge 0.1mV~1V
Signal input interface Standard BNC through coaxial cable
Measuring display mode for PD signal Waveform mode,continuous mode,phase mode
Hardware of host machine
Display 4.3 TF true color LCD screen
Screen resolution 480×272
Operation button Film button
Data Storage Standard 16G SD data storage card, 32G can also be supported
Sound input interface 3.5mm stereo headphone interface
Charging interface DC-005 LV DC charger interface
Charging indication LED indication light
Other interface RS232 Ex-factory commissioning interface
  USBD synchronous interface
  USB2.0
  Network communication port
  SD card slot
  CH1 HFCT signal interface
  US ultrasound signal interface
Supply power  
Internal supply 16.8V lithium batteries
Normal continuous working time About 7hours, charge time: about 5hour/time
Dimension
L×W×H 235mm×133mm×48mm
Weight 0.85kg
Using condition  
Using ambient temperature -20℃-50℃
Storage ambient temperature -40℃-70℃
Humidity 10%-90%,no condensing
Elevation no more than 3000m
 

Contact Details
WUHAN FANKE HAIWO HIGH VOLTAGE TECHNOLOGY CO.,LTD.

Contact Person: Sales Manager

Tel: +8613707144739

Send your inquiry directly to us