Product Details:
Payment & Shipping Terms:
|
Usage: | CT PT Volt-ampere Characteristics Tester | Test Items: | CT/PT Volt-ampere ,CT/PT Ratio, DC Resistance, |
---|---|---|---|
Other Items: | Secondary Load Test Functions, Angular Phase Difference, Secondary Withstand Voltage | Test Output: | 0-2500V Adjustable; 0-15A/0-600A/0-1000A |
DC Resistance: | Test Range : 0.1-20Ω | Secondary Load: | Test Output :0-200A |
Secondary Withstand Voltage: | Test Output: 0-2500V | Accuracy: | < 0.5% |
Highlight: | ct pt analyzer,ct pt test set |
CT PT Volt-ampere Characteristics Tester , Multifunctional CT PT Testing
I. Product Description:
With the increase requirement of relay protection, the test and check of v-c characteristic carve and the 10% error carve of instrument transformer have became more and more attracting by power system. Based on the absorbing of customers’ suggestion, Fanke has developed a new FKFA voltage-current characteristic comprehensive tester. It adopts high-speed SCM control and inset voltage-up machine, it can test CT voltage-current characteristic, 10% error curve, transformation ratio and polarity on spot. With a special voltage-up transformer, it can do a current-voltage characteristic test for CT/PT within the voltage of 500kV and the current of 1A.
II. Test items and technical data
Input voltage |
Maximum output voltage |
Maximum output current |
Power |
measurement accuracy |
|||
CT volt-ampere output |
220V | 0—2500V | 15A | 3KVA | < 0.5% | ||
CT ratio output |
220V | 0-8V | 0—600A/1000AOptional | none | < 0.5% | ||
CT ratio measurement |
The maximum ratio display: 999.9K: 5 / 1 |
< 0.5% | |||||
PT ratio measurement |
The maximum ratio display:999.9K:100,150,100/3,100/ |
< 0.5% | |||||
DC resistance measurement |
The maximum resistance measurement: 0.1-20Ω |
Less than 1Ω:3% More than 1Ω: <1% |
|||||
angular phase difference |
Minimum display: 0.01’ Accuracy::±10’ |
Ratio Difference |
Minimum display: 0.01% Accuracy:<0.5% |
||||
The secondary load test |
Output Current: 0-200A Time:1~5mins |
The secondary withstand voltage |
output Voltage: 0-2500V Time:1~5mins |
||||
Working temperature |
-10~55℃ |
Working voltage |
AC220V(±20%)50HZ | ||||
Host volume |
420×300×270 |
Host weight |
26Kg |
Contact Person: Sales Manager
Tel: +8613707144739