Product Details:
Payment & Shipping Terms:
|
Usage: | Thermal Generator Testing Machine | Test Item: | AC Hipot Test And Partial Discharge Test |
---|---|---|---|
Test Voltage: | No More Than 50KV | Test Current: | No More Than 7A |
Test Frequency: | 50Hz Or 60Hz | PD Free: | No More Than 5pC At 50KV |
Duty Cycle: | 30mints Or Made By Order | Test Accuracy: | No Less Than 1.0% |
High Light: | high voltage resonant test system,resonant test set |
Power Frequency AC Resonant Withstand Voltage Test Set , For Thermal Generators Test
I. Product Description :
According to the relevant test standards from IEC and IEEE, at the time of overhaul or new erection of the generator , the stator winding of the large capacity thermal power generator needs to conduct AC withstand voltage test at 50 or 60Hz power frequency.
AC resonant test set can be classified as variable frequency and variable inductance resonant test system. Power frequency AC resonant withstand voltage test set for large capacity thermal generators is tuned to resonance by regulating inductance. Large capacity output on test object can be obtained by inputting small capacity power supply and samll layout space through using the set. So the test set is usually used for on-site AC withstand voltage test and PD detecting HV source for power generator.The test set model CHX-350KVA/50KV is designed and used for testing 600MW and below class thermal generators .
II. Appication
600MW and below thermal generators
100MW and below hydraulic generators
III. Main Components:
SN | Name of Components | Type and specification | Qty. | Each weight | Each Dimension |
1 | Resonance Control console | DCG-L-50KVA/380V | 1piece | 25kgs | 600*360*850mm |
2 | Electric voltage regulator cabinet | DT-50KVA/0~420V | 1piece | 300kgs | 600*500*1150mm |
3 | Excitation transformer | CQSB-50kVA/8KV | 1piece | 300kgs | 650*650*800mm |
4 | Variable inductance reactor | CHX(TL)-350kVA/50kV | 1piece | 1000kgs | 950*750*1400mm |
5 | Voltage divider | TRF-50KV | 1set | 5kgs | D170*H850mm |
6 | Special test accessories | ||||
Note : Special requirement can be made by order. |
VI. General Technical data:
VI. Function
VII.Accessories
VIII. Application Sale list
SN | Project Name |
Rated capacity of generator
|
Typical model supplied of test set | Country | Order Qty. |
1 | Three Gorges Hydropower Station | 700MW Hydroelectric generator | CHX-L-2350KVA/55KV | China | 2set |
2 | Gezhouba Hydropower Station | 170MW Hydroelectric generator | CHX-L-1100KVA/40KV | China | 2set |
3 | Xiluodu Hydropower Station | 770MW Hydroelectric generator | CHX-L-2850KVA/55KV | China | 2set |
4 | Xiangjiaba Hydropower Station | 800MW Hydroelectric generator | CHX-L-3750KVA/65KV | China | 2set |
5 | Wudongde Hydropower Station | 850MW Hydroelectric generator | CHX-L-5100KVA/60KV | China | 2set |
6 | Baihetan Hydropower Station | 1000MW Hydroelectric generator | CHX-L-4800KVA/65KV | China | 2set |
7 | SON LA Hydropower Station | 400MW Hydroelectric generator | CHX-L-1125KVA/45KV | Vietnam | 1set |
IX. Optional model
Model | Rated voltage | Rated output current | Rated output capacity | Application for turbine generator or thermal power generator |
CHX-L-250KVA/50KV | 50KV | 5A | 250KVA | For 300MW and below generator stator |
CHX-L-350KVA/50KV | 50KV | 7A | 350KVA | For 600MW and below generator stator |
CHX-L-600KVA/50KV | 50KV | 12A | 600KVA | For 1000MW and below generator stator |
Special requirement can be made by order |
X. Test standard table from IEC60034-1:2017 Rotating electrical machines - Part.1 :Rating and performance
Contact Person: Sales Manager
Tel: +8613707144739