Product Details:
Payment & Shipping Terms:
|
Test Principle: | Variable Frequency Resonant Circuit | Usage: | AC Withstand Voltage Test |
---|---|---|---|
MAX.Capacity: | 9000KVA | Max.Voltage: | 150KV,300KV,450KV |
Test Frequency: | 20-300Hz | Duty Cycle: | 60 Mints |
Test Accuracy: | No Less Than 1.5% | Special For: | On-site Test For Long HV XLPE Cable And GIS |
Test Standard: | IEC 60060-1:2010;IEC 60840:2011 And IEC 62067:2011 For XLPE Cable | ||
Highlight: | ac high voltage test set,high voltage cable identifier |
Variable Frequency Resonant Withstand Voltage Test Set For Long HV XLPE Cable
I.Application :
This test set model CHX-9000KVA/150KV,300KV,450KV is designed for 132kV~400KV class long XLPE cable on-site AC hpot test and 362KV and below class GIS on-site AC hipot test with variable frequency resonant circuit technology; the highest test voltage is no more than 150KV,300KV,450KV through cylinder test reactor in parallel or in series connection ;the test frequency can be from 20-300Hz; the duty cycle is no more than 60mints.
Through modular test reactor is used in parallel or in seires, the test set model CHX-9000KVA/150KV,300KV,450KV also can be performed the following on-site AC hipot test:
1.1 No more than 150KV and 60A for long distance XLPE cable with no more than U0=87KV
1.2 No more than 300KV and 40A for long distance XLPE cable with no more than U0=160KV ;
170KV and below class GIS
1.3 No more than 450KV and 20A for long distance XLPE cable with no more than U0=230KV ;
362KV and below class GIS
Until now , these designed test set can form many different serialized model according to different HV or UHV withstand test applications through test reactors in series or in parallel connection and number of configurations in each set, The alike model can see clause 9.other typical model.
II. Main Components
SN | Name of Components | Type and specification | Qty. | Each weight | Each Dimension |
1 | Variable frequency power supply | FKVF-300kW/380V | 1piece | 280kgs | 750*700*1200mm |
2 | Excitation transformer | CQSB(J)-300kVA | 1piece | 3000kgs | 950*850*900mm |
3 | HV resonant test reactor | CHX(kf)-3000kVA/150kV | 3pieces | 4500kgs | D1200*H1250mm |
4 | Capacitive divider | TRF-450kV/1000pF | 1set | 275kgs | D250*H2850mm |
5 | Special test accessories | 1set |
Note:1.Load capacitantor can be optional when small load line is tesing or need analog load to control test frequency.
2.Test reactor can be produced to be 130KV,150KV,155KV,200KV, 250KV, 300KV, 350KV, 400KV for each piece rated voltage according to different tested object scope or customer requried. The max. rated current of each HV reactor can be 1~5A,10A,15A,20A,25A,30A.
III. Test priciple figure:
VF: Variable Frequency Power Supply Source which is control and measurement part in the test circuit.
T : Excitation Transformer which provide the exciting voltage for HV test reactor
L : Test Reactor which is resonant inductance in the LC circuit and produce the test voltage
Cx: Tested Equipment
MOA1: Lightning Arrestor is protection part on the excitation transformer
C1,C2: Voltage divider(C1 is high voltage arm,C2 is low voltage arm ) which is HV voltage measurement part
IV. General Technical data:
V. Main Measuring and control software panel as following :
Note: This figure is display panel at setting test parameter step from control and measurement software on the VF power supply
VI.Accessories
VII. Other typical model
1 Optional model for 132KV class XLPE cable on-site withstand voltage test
Model | Rated voltage | Rated output current | Rated output capacity | Max Application |
CHX-775KVA/155KV | 155KV | 5A | 775KVA | 132kV cable≤1km |
CHX-1550KVA/155KV | 155KV | 10A | 1550KVA | 132kV cable≤2km |
CHX-2325KVA/155KV | 155KV | 15A | 2325KVA | 132kV cable≤3km |
CHX-3100KVA/155KV | 155KV | 20A | 3100KVA | 132kV cable≤4km |
CHX-3875KVA/155KV | 155KV | 25A | 3875KVA | 132kV cable≤5km |
CHX-7750KVA/155KV | 155KV | 50A | 7750KVA | 132kV cable≤10km |
CHX-12400KVA/155KV | 155KV | 80A | 12400KVA | 132kV cable≤16km |
CHX-15500KVA/155KV | 155KV | 100A | 15500KVA | 132kV cable≤20km |
Special requirement can be made by order |
Note :Tested cable voltage class≤ 132kV, 0.25uF/km
2 Optional model for 230KV class XLPE cable on-site withstand voltage test
Model | Rated voltage | Rated output current | Rated output capacity | Max Application |
CHX-2020KVA/255KV | 255KV | 8A | 2020KVA | 220~230kV cable≤1km |
CHX-4080KVA/255KV | 255KV | 16A | 4080KVA | 220~230kV cable≤2km |
CHX-6120KVA/255KV | 255KV | 24A | 6120KVA | 220~230kV cable≤3km |
CHX--8160KVA/255KV | 255KV | 32A | 8160KVA | 220~230kV cable≤4km |
CHX--10200KVA/255KV | 255KV | 40A | 10200KVA | 220~230kV cable≤5km |
CHX--20400KVA/255KV | 255KV | 80A | 20400KVA | 220~230kV cable≤10km |
CHX--25500KVA/255KV | 255KV | 100A | 25500KVA | 220~275kV cable≤12.5km |
Special requirement can be made by order |
Note :Tested cable voltage class≤ 230kV, 0.25uF/km
3 Optional model for 330KV class XLPE cable on-site withstand voltage test
Model | Rated voltage | Rated output current | Rated output capacity | Max Application |
CHX-3500KVA/350KV | 350KV | 10A | 3500KVA | 330kV cable≤1km |
CHX-7000KVA/350KV | 350KV | 20A | 7000KVA | 330kV cable≤2km |
CHX-10500KVA/350KV | 350KV | 30A | 10500KVA | 330kV cable≤3km |
CHX-14000KVA/350KV | 350KV | 40A | 14000KVA | 330kV cable≤4km |
CHX-21000KVA/350KV | 350KV | 60A | 21000KVA | 330kV cable≤5km |
CHX-28000KVA/350KV | 350KV | 80A | 28000KVA | 330kV cable≤10km |
Special requirement can be made by order |
Note :Tested cable voltage class≤ 330kV, 0.25uF/km
4 Optional other model for long XLPE cable on-site withstand voltage test
Model | Rated voltage | Rated output current | Rated output capacity |
Application (From 20Hz starting) |
CHX-2600KVA/130KV | 130KV | 10A,20A | 1300KVA | For U0=64KV and below cable |
CHX-3000KVA/150KV | 150KV | 10A, 20A | 3000KVA | For U0=87KV and below cable |
CHX-10000KVA/250KV | 250KV | 20A, 40A | 10000KVA | For U0=127KV and below cable |
CHX-20000KVA/250KV | 250KV | 20A, 80A | 20000KVA | For U0=127KV and below cable |
CHX-21000KVA/350KV | 350KV | 20A, 60A | 21000KVA | For U0=230KV and below cable |
CHX-42000KVA/350KV | 350KV | 20A, 80A | 42000KVA | For U0=230KV and below cable |
Special requirement can be made by order |
Note : XLPE cable test voltage is considering as 1.7U0
5 Optional model for HV or EHV class cable and GIS On-site AC hipot test
Model | Rated voltage | Rated output current | Rated output capacity |
Application (From 20Hz starting) |
CHX-2600KVA/130KV,260KV | 130KV,260KV | 20A@130KV | 2600KVA |
For U0=64KV cable For 72.5KV class GIS |
10A@260KV |
For U0=127KV cable For 145KV class GIS |
|||
CHX-9000KVA/150KV,300KV | 150KV,300KV | 60A@150KV | 9000KVA |
For U0=87KV cable For 72.5KV class GIS |
30A@300KV |
For U0=160KV cable For 170KV class GIS |
|||
CHX-10000KVA/250KV,500KV | 250KV,500KV | 40A@250KV | 10000KVA |
For U0=127KV cable For 145KV class GIS |
20A@500KV |
For U0=290KV cable For 362KV class GIS |
|||
CHX-20000KVA/250KV,500KV | 250KV,500KV | 80A@250KV | 20000KVA |
For U0=127KV cable For 145KV class GIS |
40A@500KV |
For U0=290KV cable For 362KV class GIS |
|||
CHX-21000KVA/350KV,700KV | 350KV,700KV | 60A@350KV | 21000KVA |
For U0=190KV cable For 170KV class GIS |
30A@700KV |
For U0=290KV cable For 550KV class GIS |
|||
Special requirement can be made by order |
VIII. On-site test standard table from IEC 60840:2011 and IEC 62067:2011 for XLPE cable
IX. On-site insulation test standard table from IEC 62271-203:2011 for HV GIS