Test Principle: | Variable Frequency Resonant Circuit | Usage: | On-site AC Withstand Voltage Test |
---|---|---|---|
Design Feature:: | Highed Voltage Modular Test Reactor, Higher Q Value Output ,Multiple Test Range | Component:: | V/F Power Source, Excitation Transformer,lighter Modular Test Reactor, And Voltage Divider |
Test Frequency:: | 30-300Hz | Duty Cycle: | 15mints Or 60 Mints |
Test Accuracy: | No Less Than 1.5% | Output Waveform: | Good Sine Wave |
Special For: | On-site Test For UHV GIS , GIL , CT, PT | Test Standard:: | IEC60060-1:2010;IEC 62271-203:2011 For GIS |
High Light: | high voltage resonant test system,resonant test set |
Variable Frequency Resonant Withstand Voltage Test Set , High Voltage Test Set For UHV Substation or GIS
I. Application :
This series of test system mainly aims at AC voltage withstand test of primary equipment of large capacitor and high voltage and can also satisfy field AC voltage withstand test of sorts of capacitance apparatus. HV test reactors use combined series-parallel patterns which not only meet the requirements of voltage withstand of HV transformer, GIS, SF6 breakers,mutual inductions and bushings but also that of long distance XLPE cables ,with compatibility of extensive tests to be a desired voltage withstand test device for power supply system overhauling and electric power engineer construction units.
The above picture is for variable series resonance test system of 5000KVA/1000KV on test field in Shanxi Jindongnan Substation, testing HV
GIS of 1000KV class UHV line in domestic.
Applicable objects
- Long distance XLPE cables with 110KV,220KV,500KV class
- HV GIS or GIL, HV coupling capacitor,capacitor voltage transformer of no more than 1000KV class
- Assembling capacitor(test frequency pledges in 45—65Hz)
II. Main Components:(4000KVA/1000KV test system for example)
SN | Name of Components | Type and specification | Qty. | Each weight | Each Dimension |
1 | Variable frequency power | FKVF-200kW/380V | 1piece | 180kgs | 750*700*1000mm |
2 | Excitation transformer | CQSB(J)-200kVA | 1piece | 1800kgs | 650*650*800mm |
3 | HV resonant test reactor | CHX(kf)-800kVA/200kV | 5pieces | 2800kgs | D1200*H1250mm |
4 | Capacitive divider | TRF-1000kV/1000pF | 1set | 550kgs | D350*H7600mm |
5 | Special test accessories | 1set |
Note:1.Load capacitantor can be optional when small load line is tesing or need analog load to control test frequency .
2.Test reactor can be produced to be 150KV,200KV,250KV,300KV, 350KV, 400KV for each piece rated voltage according to different tested object scope or customer requried. The max. rated current of each HV reactor can be 1~15A optional in this serialized set,
3. HV Damping inductance can be optional for suppressing high frequency harmonics and resisting overvoltage caused from tested object flashover, special in EHV or UHV test set.
III. Test priciple :
VF: Variable Frequency Power Source T : Excitation Transformer
L : Test Reactor Cx: Tested Equipment MOA1: Lightning Arrestor
C1,C2: Voltage divider(C1 is high voltage arm,C2 is low voltage arm )
IV. General Technical Data:
V. Technical Feature and advantage
VI. Main Measuring and control software panel as following :
VII.Accessories
VIII. Other Typical Model
1 For 123KV ~300KV class GIS on-site AC hipot test
Model | Rated voltage | Rated output current | Rated output capacity |
Application (From 45Hz starting) |
CHX-400KVA/200KV,400KV | 200KV*2 | 2A@200KV | 400KVA | For 123KV and below class GIS |
1A@400KV | For 300KV and below class GIS | |||
CHX-800KVA/200KV,400KV | 200KV*2 | 4A@200KV | 800KVA | For 123KV and below class GIS |
2A@400KV | For 300KV and below class GIS | |||
CHX-1000KVA/200KV,400KV | 200KV*2 | 5A@200KV | 1000KVA | For 123KV and below class GIS |
2.5A@400KV | For 300KV and below class GIS | |||
CHX-2000KVA/200KV,400KV | 200KV*2 | 10A@200KV | 2000KVA | For 123KV and below class GIS |
5A@400KV | For 300KV and below class GIS | |||
Special requirement can be made by order |
2 For 145KV ~362KV class GIS on-site AC hipot test
Model | Rated voltage | Rated output current | Rated output capacity |
Application (From 45Hz starting) |
CHX-500KVA/250KV,500KV | 250KV*2 | 2A@250KV | 500KVA | For 145KV and below class GIS |
1A@500KV | For 362KV and below class GIS | |||
CHX-1000KVA/250KV,500KV | 250KV*2 | 4A@250KV | 1000KVA | For 145KV and below class GIS |
2A@500KV | For 362KV and below class GIS | |||
CHX-2000KVA/250KV,500KV | 250KV*2 | 8A@250KV | 2000KVA | For 145KV and below class GIS |
4A@500KV | For 362KV and below class GIS | |||
CHX-3000KVA/250KV,500KV | 250KV*2 | 12A@250KV | 3000KVA | For 145KV and below class GIS |
6A@500KV | For 362KV and below class GIS | |||
Special requirement can be made by order |
3 For 170KV ~550KV class GIS on-site AC hipot test
Model | Rated voltage | Rated output current | Rated output capacity |
Application (From 45Hz starting) |
CHX-1200KVA/300KV,600KV | 300KV*2 | 4A@300KV | 1200KVA | For 170KV and below class GIS |
2A@600KV | For 550KV and below class GIS | |||
CHX-1800KVA/300KV,600KV | 300KV*2 | 6A@300KV | 1800KVA | For 170KV and below class GIS |
3A@600KV | For 550KV and below class GIS | |||
CHX-2400KVA/300KV,600KV | 300KV*2 | 8A@300KV | 2400KVA | For 170KV and below class GIS |
4A@600KV | For 550KV and below class GIS | |||
CHX-3600KVA/300KV,600KV | 300KV*2 | 12A@300KV | 3600KVA | For 170KV and below class GIS |
6A@600KV | For 550KV and below class GIS | |||
CHX-4800KVA/300KV,600KV | 300KV*2 | 16A@300KV | 4800KVA | For 170KV and below class GIS |
8A@600KV | For 550KV and below class GIS | |||
Special requirement can be made by order |
4 For 123KV ~800KV class GIS on-site AC hipot test
Model | Rated voltage | Rated output current | Rated output capacity |
Application (From 45Hz starting) |
CHX-2400KVA/200KV×4 | 800KV | 12A@200KV | 2400KVA | For 123KV and below class GIS |
6A@400KV | For 300KV and below class GIS | |||
3A@600KV | For 550KV and below class GIS | |||
3A@800KV | For 800KV and below class GIS | |||
CHX-3600KVA/200KV×4 | 800KV | 13A@200KV | 3600KVA | For 123KV and below class GIS |
9A@400KV | For 300KV and below class GIS | |||
4.5A@600KV | For 550KV and below class GIS | |||
4.5A@800KV | For 800KV and below class GIS | |||
CHX-4800KVA/200KV×4 | 800KV | 24A@200KV | 4800KVA | For 123KV and below class GIS |
12A@400KV | For 300KV and below class GIS | |||
6A@600KV | For 550KV and below class GIS | |||
6A@800KV | For 800KV and below class GIS | |||
Special requirement can be made by order |
IX. On-site insulation test standard table from IEC 62271-203:2011 for HV GIS