Product Details:
Payment & Shipping Terms:
|
Usage: | High Voltage Peak Value Measurement | Applied For: | Lighting Impulse Test System |
---|---|---|---|
Accuracy: | 0.2 / 0.5 Class (Uin> 0.2V) | Signal Range: | 0 ~ 600 V RMS AC ; 0 ~ 900V Peak DC |
Signal Input Interface: | Standard BNC , Standard R16 | Special Function: | Hold And Display Breakdown HV Value |
Highlight: | peak voltage tester,peak voltage multimeter |
Digital Multi-function Peak Voltage Meter With High Accuracy , Matched With Lighting Impulse Test
I. Product Description
Model PV2-1 digital multi-function AC / DC peak voltage meter is applied for measuring and mornitoring High voltage test voltage value in AC withstand voltage test or lighting impulse test system . it can be designed to be two different profiles, one type is the standard 19-inch box-type with plug-in , and another type is compact 4U chassis. The voltmeter can distinguish AC and DC voltage signals automatically, at the same time, also have the functions of voltage signal measurement, breakdown HV monitoring and holding, over-voltage alarm and rapid protection, etc. The accuracy is up to 0.5 or 0.2 class.
The voltmeter uses advanced DSP processor and digital signal processing technology to complete computation, measurement and analysis. By real-time signal waveform capture and analysis, the meter can accurately judge the instant at which the HV breakdown occurs, hold the voltage value at this time and inform the user in-time afterwards by the relay action. The advanced EMC design make the meter run reliably in long-time high electric field and magnetic field environment. PV2-1 is leading to its competitor wherever the domestic and abroad.
II. Parameters
Parameters: | |
Signal measure range | AC 0--600 V , DC 0--900V |
Signal measure accuracy | 0.2% or 0.5%(Uin> 0.2V) |
Input impedance | > 2MΩ |
Relay Terminals | I<0.5A , U<250V |
Relay Response time | < 20ms |
Control Delay of HV Breakdown Relay | 3s |
Power supply | ~220V/20VA |
Working temperature | -15℃ -- 55℃ |
Signal input terminals | BNC , R16 |
AC K1 voltage ratio setting range | 0.01 - 99999.99 |
DC K2 voltage ratio setting range | 0.01 - 99999.99 |
Over-voltage limit setting range | 0.01 - 99999.99 kV |
Record breakdown voltage limit range | 0.01 - 99999.99 kV |
Dimension: | about 90mm*228mm*300mm |
Weight: | about 10KG |
III .Measurement functions
IV. Matched with high-voltage test set
Contact Person: Sales Manager
Tel: +8613707144739